Specifications and Technology

Corrugated stainless steel pipe and fittings: diameter, pressure and bending

Understanding diameters, thread designations, wall thickness, working pressure and burst pressure for corrugated stainless steel pipe. Temperature, bending and fitting compatibility.

Specifications and technology / Pipes and fittings

Choose the pipe and fitting as an assembly. Matching 1/2-inch or 3/4-inch labels is only the start. Check pipe profile, connection, seal, fluid, temperature and pressure. Several of these specifications can be easily confused in a product listing.

Outside and inside diameters: what is measured?

Outside diameter describes the outer dimension of the profile, and inside diameter describes the internal bore. On corrugated pipe, crests and troughs have different dimensions. Use the measurement locations indicated on the manufacturer’s drawing. A value of 18.1 ± 0.1 mm is a nominal dimension with a tolerance. The inside diameter matters for fluid passage, but flow also depends on run length, resistance and operating conditions. Witzenmann’s guide to corrugated metal hose geometry distinguishes corrugation features and bending parameters. Obtain the dimensions of the particular pipe from its drawing rather than estimating them from a diagram.

Why half the difference in diameters may not equal the wall thickness

On a plain round pipe, the difference between outside and inside diameters relates directly to wall thickness. That comparison cannot be applied blindly if the diameters were measured at different parts of a corrugation. For example, subtracting 15.1 mm from 18.1 mm does not prove that a stated 0.25 mm wall thickness is wrong. Establish how each dimension was measured. Wall thickness describes the metal itself. It is not a strength rating and cannot by itself establish the permissible pressure of different pipe series.

Longitudinal corrugation profile showing three different dimensions: outside diameter, internal bore and metal wall thickness. Diagram not to scale.
Longitudinal corrugation profile showing three different dimensions: outside diameter, internal bore and metal wall thickness. Diagram not to scale. Technical reference: Witzenmann’s guide to corrugated metal hose geometry.
ParameterWhat to check
Outside / inside diameterDrawing, measurement location and tolerance
Wall thicknessThickness of the metal rather than corrugation height
ThreadNominal size, standard, male or female thread and sealing method
Working pressureTemperature and allowable operating conditions
Burst pressureTest conditions rather than an operating rating
Short-term temperatureDuration and limits for the complete assembly
Bend testMethod, radius and type of movement

Fitting threads: size, standard and gender

The 1/2-inch and 3/4-inch designations on pipe threads are nominal sizes. They do not imply calliper readings of 12.7 or 19.05 mm. A female thread is inside the connection and a male thread is on its outside. Check the standard and geometry separately: G/BSPP, R/Rp and NPT should not be treated as interchangeable. Swagelok’s thread identification guide compares diameter, pitch, taper and sealing method. Size and gender alone do not identify the standard. A fitting must be compatible with both the pipe and the mating threaded connection. Never force threads together to test whether they fit.

Working, test and burst pressures

Working pressure is the limit under specified operating conditions. Test pressure applies to a defined verification procedure. Burst pressure describes sample failure under test conditions. Senior Flexonics defines these three ratings separately. A high burst pressure does not permit operation near that value. Never derive working pressure by dividing burst pressure by a factor of your own choosing. The assembly also depends on fittings, seals and loading conditions. Have a qualified specialist test it using the specified procedure. Never try to test it to destruction yourself.

Reading 15 bar, 1.6 MPa and 210 bar in a catalogue

1 MPa equals 10 bar, so 1.6 MPa equals 16 bar rather than 15. If a listing gives both “working pressure 1.6 MPa” and “maximum working pressure at operating temperature 15 bar”, the entries are not simple unit conversions. They may refer to different conditions or there may be a data error. Consult the data sheet to clarify the temperature, fluid and configuration. Even the lower number is not automatically a verified safe operating point. “Burst pressure 210 bar at 20 °C” describes a separate test and does not resolve the discrepancy. These examples identify what to verify rather than certify the ratings of a particular product.

Temperature: continuous operation and short-term maximum

The maximum short-term temperature is not a continuous operating rating. For a figure of 200 °C, check the permitted duration, pressure, fluid and conditions for every part of the joint. Do not combine independently quoted maximum pressure and temperature into one operating point. IBK shows how a temperature factor affects allowable pressure. Do not use another series’ table to calculate your pipe’s rating. A fitting seal may have a different temperature limit from the pipe metal. Verify that the entire assembly is suitable for the intended fluid. Suitability for water does not establish suitability for gas or steam.

What a bend test tells you

Figures such as “14 times” or “18 times” do not establish service life without the test method. Check the radius, angle, pressure, conditions and test endpoint. They do not specify how many times an installed run may be reworked. A fixed installation and repeated movement impose different requirements. Witzenmann distinguishes bend radii for one-time and repeated movement. Flexible corrugations do not justify tight kinks, flattening or twisting. Follow the specific product’s instructions for bend radius and support. Do not conceal a damaged section beneath a fixing or straighten it again for continued use without professional assessment.

What to establish before ordering a fitting

Identify the pipe series and size, mating thread standard and gender, fluid, pressure and temperature range. Confirm seal material and approved component combinations. Similar appearance does not establish a matching seat profile. Substituting a similar nut or seal requires a solution approved by the manufacturer. Have a qualified specialist assemble, leak-test and commission the installation. For specialist applications including gas, a general “stainless steel pipe” label is insufficient.

Checks before choosing

  1. Match the pipe and fitting using the series documentation.
  2. Check the thread standard and gender.
  3. Resolve conflicting pressure ratings and units before connection.
  4. Clarify continuous and short-term temperature limits.
  5. Have a qualified specialist install and leak-test the assembly.

Frequently asked questions

May I operate at 210 bar if it appears in the specifications?

No, if the figure is the burst pressure. That value does not establish allowable operation.

Are 1.6 MPa and 15 bar equivalent?

No. 1.6 MPa equals 16 bar. If a listing gives both figures, check the conditions in the data sheet.

Will any 1/2-inch fitting work?

No. Check pipe series, thread standard, thread gender and sealing method.

Do 18 bends mean 18 permitted reinstallations?

No. Without the test method, the figure cannot establish service life in your application.

In brief
Select a compatible assembly. Diameter, thread, working pressure, temperature and bend radius must all apply to the same verified configuration.

Next step

Need help with privacy, secure internet, or infrastructure? Describe the task and we will suggest a practical setup.

Get consultation

Related articles